|
Current Ratings / Accuracy Ratings
|
Voltage Ratings
|
Current Ratings:
Most Polycast current transformers are available as single, double or multi-ratio units. Five amp secondaries are standard, but one amp secondaries are available for most styles. Maximum and minimum primary ratings depend upon the style selected.
Accuracy Ratings:
For most applications the simplicity and high mechanical withstand capability of window type and bar type current transformers makes them preferable for most applications. Wound primary current transformers are recommended where very high accuracy at lower ratios (5-5A through 300-5A) is required.
Testing:
Polycast testing capabilities include polarity, ratio and phase angle, saturation, temperature rise, open circuit, induced, power factor, hipot, impulse, partial discharge, low temperature withstand and other physical and mechanical testing.
All Polycast current transformers are individually tested.
Routine and type test reports are available on request.
|
|
Polycast
Standard
Designation |
Nom.
Voltage
Class kV |
Low
Freq.
Dry
kV |
Impulse
kV Crest
1.2x 50us |
Chopped
Wave
kV Crest
(us)
|
| 0.6 |
0.7 |
4 |
10 |
12 (1.0) |
| 05 |
5.0 |
19 |
60 |
69 (1.5) |
| 08 |
8.7 |
26 |
75 |
88 (1.6) |
| 15 |
15.0L |
34
|
95 |
110
(2.0) |
| 18 |
15.0H |
36 |
110 |
130 (2.0) |
| 25 |
27.5L |
50 |
125 |
145 (3.0) |
| 28 |
27.5H |
60 |
150 |
175 (3.0) |
|
The above values are based upon, and are intended to meet the most stringent requirements of, the following standards: ANSI/IEEE C57.13, CSA CAN3-C13 and IEC 185
|
Material Standards:
- Cores are grain-oriented silicon steel (M4 or higher), annealed after forming, to provide maximum accuracy.
- Core insulation is electrical grade pressboard and kraft paper, or epoxy.
- Secondary coils are 200C rated copper magnet wire with silver soldered connections to terminals or leads, and high quality electrical grade kraft or nomex interlayer insulation.
- Primaries (where provided) are electrolytic copper, electroplated with silver.
- Cast indoor units are manufactured from bis-A epoxy.
- Cast outdoor units are manufactured of cycloaliphatic epoxy, and are complete with weatherproof terminal boxes.
- All current transformers are nameplated and have prominent polarity markings.
Some Standard Terminology:
| Turns Ratio |
the ratio of the secondary turns to one. |
| Current Ratio |
the ratio of the primary current to the secondary current in amps. |
| TCF |
The correction for the overall error due to both ratio and phase angle error for a specified primary circuit power factor. |
| RCF |
Ratio Correction Factor is the ratio of the true ratio to the marked ratio (excitation & other losses result in ratio error). |
| Rated Burden |
The maximum load which may be placed on the current transformer secondary without causing an error greater than that allowed by the stated accuracy (in ohms impedance, e.g. B0.1, B0.9, B2 or corresponding volt-ampere values of 2.5, 22.5, 50 VA). |
Accuracy Class
Metering
Relaying |
Metering Accuracy = the TCF shall be within specified limits at 10%, 100%, and CCRFx100% at a given power factor with a specified burden. Relaying Accuracy= the composite error shall not exceed a specified percentage error at a specified secondary terminal voltage based on a maximum fault level of secondary current. |
| CCRF |
Continuous Current Rating Factor is the factor by which the rated current of the current transformer can be multiplied to obtain the maximum continuous current that the current transformer can carry without exceeding the temperature rise or accuracy requirements. |
1 Sec Thermal
Withstand |
The maximum rms symmetrical primary current that can be carried for one second with the secondary short circuited without exceeding the limiting temperature. |
Mechanical
Withstand |
The maximum rms asymmetrical primary current that a current transformer can carry with the secondary short circuited without any damage which would render it incapable of meeting other standard accuracy and transformation requirements. |
Special Considerations:
- Current Transformers should never have primary current injected with the secondaries open-circuited. This is especially true at higher current ratios (1200-5A and above) where open circuit voltage may exceed 3500 volts (OC standard test voltage limit).
- The test standard and any special requirements for each current transformer ordered should be specified on the purchase order.
Because the conditions of use of any current transformer is beyond the control of the supplier, it is always the responsibility of the user to ensure that the current/voltage ratings and the accuracy of the transformer used is adequate for their application.
|